EasyManua.ls Logo

AUMA EPAC - 4-20 mA Signal Fail Troubleshooting; LCD Display - Local Mode Issue; Blank LCD Display Troubleshooting

AUMA EPAC
49 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
46
b) If the voltages are not proper, it means relay failure on the PS card. Replace the PS
card.
XIII. 4-20mA Signal Fail:
TROUBLESHOOT:
a. Check if 4-20mA values in Diagnostic Mode are less than 30 or greater than 2000.
b. Under Remote-regulating duty mode we have to give 4-20mA DC Current
from external DC source to the respective terminals (as per WD) named
with ferrule “II+” and “II-“.
c. Check the connectivity of J5 connector at the Interface Board and also verify
the wiring with respect to WD and ensure that the 4- 20mA input is coming
from DCS.
d. If the 4-20mA values in Diagnostic Mode is correct and a signal fail still occurs, then replace the
IF card.
XIV. Mode selected in Local option is not displaying on the LCD screen: This problem arises
if “Remote Sel. Switch” option is enabled. To disable this option, enter into the
Program Mode General Settings
XVI. LCD Display is blank with back light ON:
Check whether all respective connectors are plugged properly and ensure that the shorting
link is connected properly on J2, J3 & J19 of CPU card as shown below.
K
K
K1
K2
Fig. O: CONTACTOR
Fig. E: Contactor