Digital Counter / Timer / Tach User Manual, 1st Ed.
2-115
www.automationdirect.com
Dual Counting (
dUAL
)
A single count setting value SV is available in Dual Counting. Both Outputs 1 and 2 operate concurrently and
will turn ON momentarily for the time set in the output pulse width parameter (tout2) or will be maintained ON
depending on the Output Mode selected.
CTT Counter Functions
Dual Counting (dual)
Addition (add)
Addition (
Add
)
Each leading edge of the input signal at CP1 will increment the count present value PV by 1.
Input Mode:
Mode F (
F
)
When the count present value PV counts up to the count
setting value SV both outputs 1 and 2 will turn ON. The count
PV will continue to increment with each input signal.
The leading edge of a “reset” input signal at RST1 will turn
OFF both outputs, reset the count present value PV to 0, and
prohibit an input signal from incrementing the count PV. The
trailing edge of the “reset” signal at RST1 enables counting to
begin.
The “reset” signal minimum pulse width is set by reset pulse
width parameter (
rtSr
) or DIP Switch 8.
Output Modes:
Each leading edge of the input signal at CP2 will increment the count present value PV by 1.
999999
RESET
SV
OUT2
OUT1
PV
DUAL
Input Mode ADDITION
0
Mode N (
n
)
When the count present value PV counts up to the count
setting value SV both outputs 1 and 2 will turn ON. The count
PV will remain at the count SV regardless of additional input
signals.
The leading edge of a “reset” input signal at RST1 will turn
OFF both outputs, reset the count present value PV to 0, and
prohibit an input signal from incrementing the count PV. The
trailing edge of the “reset” signal at RST1 enables counting to
begin.
The “reset” signal minimum pulse width is set by reset pulse
width parameter (
rtSr
) or DIP Switch 8.
RESET
999999
SV
PV
OUT2
OUT1
DUAL
Input Mode ADDITION