DL06 Micro PLC User Manual; 3rd Edition Rev. E
4–16
Chapter 4: System Design and Configuration
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
Example 1: V2100 584/984 Mode
Find the MODBUS address for User V location V2100. PLC Address (Dec.) + Mode Address
1. Find V-memory in the table. V2100 = 1088 decimal
2. Convert V2100 into decimal (1088). 1088 + 40001 =
3. Add the MODBUS starting address for the
mode (40001).
Example 2: Y20 584/984 Mode
Find the MODBUS address for output Y20. PLC Addr. (Dec.) + Start Address + Mode
1. Find Y outputs in the table. Y20 = 16 decimal
2. Convert Y20 into decimal (16). 16 + 2048 + 1 =
3. Add the starting address for the range (2048).
4. Add the MODBUS address for the mode (1).
Word Data Types
Registers
PLC Range
(Octal)
Input/Holding
(484 Mode)*
Input/Holding
(584/984 Mode)*
V-memory (Timers)
V0 - V377 3001/4001 30001/40001
V-memory (Counters)
V1000 - V1177 3513/4513 30513/40513
V-memory (Data Words)
V1200 - V1377 3641/4641 30641/40641
V1400 - V1746 3769/4769 30769/40769
V1747 - V1777 --- 31000/41000
V2000 - V7377 --- 41025
V10000 - V17777 --- 44097
1. Refer to your PLC user manual for the correct memory mapping size of your PLC. Some of
the addresses shown above might not pertain to your particular CPU.
2. For an automated MODBUS/Koyo address conversion utility, go to our website
wwww.automationdirect.com, and down load download the EXCEL file
modbus_conversion.xls located at: Tech Support > Technical Support Home page.
41089
For Word Data Types.... PLC Address (Dec.) + Appropriate Mode Address
Timer Current Values (V) 128 V0 – V177 0 – 127 3001 30001 Input Register
Counter Current Values (V) 128 V1200 – V7377 640 – 3839 3001 30001 Input Register
V-memory, user data (V) 1024 V2000 – V3777 1024 – 2047 4001 40001 Holding Register
2065
Outputs (Y) 320 Y0 - Y477 2048 – 2367 1 1 Coil
Control Relays (CR) 256 C0 - C377 3072 – 3551 1 1 Coil
Timer Contacts (T) 128 T0 - T177 6144 – 6271 1 1 Coil
*MODBUS: Function 04