DL06 Micro PLC User Manual, 3rd Edition, Rev. E
5-31
Chapter 5: Standard RLL Instructions
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
In the following example, when the value in BCD V-memory location V2000 = 5000, and
V2002 M 2345, Y3 will energize.
In the following example, when the value in V-memory location V2000 = 7000 and
V2002 < 2500, Y3 will energize.
A aaa B bbb
A aaa B bbb
ENT
3
D
2
C
3
D
4
E
5
F
ENT
ENT
0
A
0
A
5
F
0
A
2
C
Y3
OUT
V2000 K5000
V2002 K2345
DirectSOFT32
Handheld Programmer Keystrokes
STR
$
SHFT
4
E
0
A
0
A
0
A
AND
V
OUT
GX
SHFT
AND
V
2
C
0
A
0
A
2
C
2
C
5
F
ENT
0
A
0
A
7
H
ENT
0
A
0
A
0
A
2
C
Y3
OUT
V2000
K7000 V2002 K2500
DirectSOFT32 Handheld Programmer Keystrokes
STR
$
SHFT
4
E
2
C
0
A
0
A
0
A
ANDN
W
OUT
GX
SHFT
AND
Y
ENT
3
D
SHFT
AND
V
2
C
0
A
0
A
Operand Data Type DL06 Range
A/B
aaa bbb
V-memory V See memory map See memory map
Pointer p See memory map See memory map
Constant K –– 0–9999
Timer TA 0–377
Counter CTA 0–177
DS Implied
HPP Used
DS Implied
HPP Used
DirectSOFT
DirectSOFT
And (AND)
The Comparative And instruction connects a normally
open comparative contact in series with another contact.
The contact will be on when Aaaa is equal to or greater than
Bbbb.
And Not (ANDN)
The Comparative And Not instruction connects a normally
closed comparative contact in series with another contact.
The contact will be on when Aaaa < Bbbb.