DC inverter ARV Individual Series technical manual
87
3.8Electric Characteristic
Model
Unit
Power supply
OFM
Hz
Voltage
(V)
MCA
(A)
MFA
(A)
Output power
(W)
FLA
(A)
ARV-H615/5R1B
50
380-415V
36.20
50
750*2
3.50
ARV-H670/5R1B
50
380-415V
41.90
50
750*2
3.50
ARV-H730/5R1B
50
380-415V
57.90
80
750*3
3.50
ARV-H780/5R1B
50
380-415V
58.86
80
750*3
3.50
ARV-H850/5R1B
50
380-415V
64.13
80
750*3
3.50
ARV-H900/5R1B
50
380-415V
65.28
80
750*3
3.50
Symbols:
MCA: Min. Circuit Amps. (A);
MFA: Max. Fuse Amps. (A);
OFM: Outdoor Fan Motor;
FLA: Full Load Amps. (A);
Note:
1. RLA is based on the following conditions, Indoor temp. 27°C DB/19°C WB, Outdoor temp. 35°C DB.
2. Maximum allowable voltage variation between phase and phase is 2%.
3. Selection wire size based on the larger value of MCA.
4. MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth circuit breaker).

Table of Contents

Other manuals for AUX ARV Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AUX ARV Series and is the answer not in the manual?

AUX ARV Series Specifications

General IconGeneral
BrandAUX
ModelARV Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals