CTR INSTALLATION GUIDE
Circuit Overloading
When connecting the CTR, determine the effect this will have on the power
supply circuit protection devices, and supply wiring. Check CTR power
consumption specifications and the supply capability of the power supply
system. This check of capacity must extend to the dc power supply and not
just to an intermediate connection point.
Mechanical Loading
When installing an indoor unit in a rack, ensure the rack is securely
anchored. Ensure that the additional loading of a CTR indoor unit or units
will not cause any reduction in the mechanical stability of the rack.
Fan Blades
CAUTION: Fan card houses hazardous moving parts.
Restricted Access
CTR 8540 must be installed in restricted access sites. The indoor unit and
associated power supply must be installed in restricted areas, such as ded-
icated equipment rooms, closets, cabinets, or the like. Access to any tower
and antenna location must be restricted.
For USA:
In restricted access areas install the CTR system in accordance with articles
110-26 and 110-27 of the 2002 National Electrical Code ANSI/NFPA 70, or to
any subsequent update to this code for the relevant articles.
END