AB-6546 
 
1 
Specifications/Instructions
 
Operator Panel 
for Infilex
™
 AC / Infilex
™
 GC / Infilex
™
 GD 
Model QY5100W0000 (Panel Mount Type) 
Model RY5001Q0000 (Integral Type) 
 
General 
Operator Panel is a user terminal for data display and 
configuration, which can be connected to a remote unit: 
Infilex AC, Infilex GC, or Infilex GD.  Two types of Operator 
Panel are available.  Panel mount type (Model 
QY5100W0000) is mounted on the door of the control 
panel cabinet.  Integral type (Model QY5100W0000) is 
attached directly to the remote unit or to its I/O module to 
integrate with the remote unit. 
The Operator Panel can display all the points that the 
remote unit has.  Points to be modified (by changing their 
data configuration) or operated, such as parameters, AO 
(analog output), and DO (digital output), can be modified or 
operated through the Operator Panel. 
By connecting the Operator Panel to a remote unit (Infilex 
AC, Infilex GC, or Infilex GD), the remote unit can be 
managed not only through client PC of our BMS (building 
management system), savic-net
™
 FX, but also through the 
Operator Panel at the installation site.  This greatly 
improves the efficiency of the building management. 
Additionally, the Operator Panel facilitates status indication 
of the points, and allows a remote unit to be easily used as 
standalone. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Features 
•  Display of points: 
All points of the remote unit can be managed through 
the Operator Panel. 
The Operator Panel displays the points as follows: 
- Group-points mode  
  Points divided into up to 4 groups are displayed 
 per group. 
- All-points mode 
  All the points of the remote unit  are displayed. 
The points that can be modified or operated through the 
Operator Panel can be modified or operated in either 
mode.  Additionally, one point selected among the 
ON/OFF points and the alarm points of the remote unit 
can be continuously displayed. 
• Operation restriction: 
ON/OFF operation and data configuration change 
through the Operator Panel can be restricted. 
 
•  Functions for a standalone remote unit: 
When the remote unit connected to the Operator Panel 
is standalone, an operation schedule of the point 
specified to continuously display its status can be set 
through the Operator Panel.  Additionally, the Operator 
Panel has a manual override function for AO and DO. 
•  LCD backlight and LED: 
Model QY5100W000 is equipped with an LCD 
backlight, and Model RY5001Q0000 is equipped with 
a 7 segment LED.  Operator Panel thus displays the 
data and allows the operators to operate even in a 
dark place. 
•  CE Marking certified product: 
Operator Panel (both panel mount type and integral 
type) conforms to all the applicable standards of CE 
Marking (Class A). 
 
 
Model QY5100W0000 
(Panel mount type) 
Model RY5001Q0000 
(Integral type)