Chapter 3. MOUNTING AND WIRING
When connecting the MCF to a pipe 1 size smaller than the MFC port (for example, the MFC0150 to
a 1/4 inch pipe), to determine the straight pipe length use the section of the table marked “Pipe one
size smaller in dia. (connected with reducer).” In addition, on the upstream side add 5D to the
straight pipe length.
* The specified length is the straight pipe length when connecting a pipe one size smaller than the
MCF.
Note 7: The figures below show examples of connection with a single elbow and double elbow.
Note 8: This valve does not have an internal throttle. If possible, install a flow regulating valve downstream
from the MCF.
Note 9: A regulator should be 200D away from this device. The pipe from the regulator to this device may be
consist of an air tube and elbow. However, if the elbow is connected to this device, use the neces-
sary straight pipe section for the elbow.
200D or more.
30D or more.