What to do if excessive fluid leaks downstream of the Azbil Control Unit valve?
- PPeter RossAug 10, 2025
If you observe excessive fluid leaking downstream of the Azbil Control Unit valve, even when the valve opening is unchanged, several factors could be at play. First, check for air leakage in the actuator by applying supply air or atmospheric pressure and inspecting the air source and positioner. Also, verify if the valve opening is truly at zero by checking the lift. Finally, inspect the plug or seat ring for corrosion or erosion, and check for any jamming on the guide. Replacement of parts may be required.