GENERAL INFORMATION
Operating conditions
BAC cooling equipment is designed for the operating conditions specified below, which must not be exceeded
during operation.
Wind Load: For safe operation of unshielded equipment exposed to wind speeds above 120 km/h installed at a
height above 30 m from the ground, contact your local BAC-Balticare representative.
Seismic Risk: For safe operation of equipment installed in moderate and high hazard area's contact your local
BAC-Balticare representative.
Standard electrical motors are suitable for an ambient temperature range from -25°C to +4C.
Design pressure: max. 10 bar
Fluid inlet temperature: max. 8C
Fluid outlet temperature: min. 10°C
Fluids circulated through the inside of the coils must be compatible with the coil construction material, ie.
- black steel, for hot dip galvanized coils
- stainless steel AISI 304L or 316L (options)
- galvanized steel for cleanable coil (option)
Maximum spray pressure: 14 kPa (If pump(s) are installed by others, it is recommended to install a pressure gauge
at the inlet of the water distribution system.)
Stand-by pump arrangements for evaporative fluid coolers require alternating operation of each pump at
least twice per week to avoid stagnant water conditions and bacteriological growth.