14 Instruction 3015-4149
10. Press the “LEAK LEVEL” button. Use left/right keys to move across and up/down keys to readjust
leak alarm PPM level to desired PPM level.
11. Press the “SPILL LEVEL” button. Repeat as in step 10.
NOTE: The spill level must be greater than or equal to the leak level.
12. Press the “EVACUATE LEVEL” Button. Repeat as in step 10.
NOTE: The evacuate level must be greater than or equal to the spill level, which must be greater
than or equal to the leak level.
13. Press the “RESET PEAK” button. Used to clear the previous peak PPM displayed for this zone. This
key is used to clear the peak PPM for this zone, which is displayed at the top of this screen. The peak
PPM gives the PPM level, time and date of the highest refrigerant readings since the unit was last
cleared (or started, if the reading has never been cleared). The peak PPM reading along with the
TREND DATA can be a powerful diagnostic tool in detecting small leaks before they become large
leaks.
14. To move to the next zone’s setup screen, press the right keypad button. Press the “BACK” button to
move to that zone’s first setup screen. Repeat steps 2 thru 13 to program the second zone. Repeat
as necessary for all zones in monitor.
15. To return to the System Screen, press “QUIT” then press “SYSTEM”.
Zone Setup Screen #2

Other manuals for Bacharach HGM300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bacharach HGM300 and is the answer not in the manual?

Bacharach HGM300 Specifications

General IconGeneral
BrandBacharach
ModelHGM300
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals