HGM-MZ Multi-Zone Monitor
Annual Maintenance
And Troubleshooting Guide
Service, Testing and Maintenance procedures

Other manuals for Bacharach HGM-MZ

Questions and Answers

  • Y
    Yvette BergJul 27, 2025
    What causes 'ZERO FILTER FAULT (0100)' in Bacharach Measuring Instruments?
    • D
      David KingJul 27, 2025
      A 'ZERO FILTER FAULT (0100)' in your Bacharach Measuring Instruments indicates contamination in the purge air. This could be due to dirt, water, or refrigerant in the charcoal purge filter, meaning the charcoal filter may need replacement. Also, ensure the purge line has a filter on the end (line end filter p/n 3015-3420) and that the purge air comes from a clean, dry source.
  • T
    Tony OwensJul 31, 2025
    What to do if Bacharach HGM-MZ Measuring Instruments show 'NO FLOW ON PURGE (1000)' fault code?
    • J
      Jennifer Wood MDJul 31, 2025
      If your Bacharach Measuring Instruments display a 'NO FLOW ON PURGE (1000)' fault code, check the following: 1. Examine the purge line for blockages on the line end filter or charcoal purge filter. 2. Check the Hydrophobic filter for blockage of dirt or water; if water is present, identify and eliminate its entry point into the monitor. 3. Confirm the pump is running. 4. Verify the pressures on the Diagnostic screen. 5. Ensure the combined length of the purge line and exhaust line does not exceed 500 feet.
  • Y
    Yvonne MatthewsAug 4, 2025
    What does 'GAIN SET FAULT (0200)' mean on Bacharach HGM-MZ Measuring Instruments?
    • C
      Clifford FloydAug 5, 2025
      A 'GAIN SET FAULT (0200)' in Bacharach Measuring Instruments indicates the sensor gain (digipot) is outside the acceptable range. Consult the HGMMZ voltage adjustment bulletin. If the fault persists, it could signal a failing IR sensor.
  • J
    Jessica WilliamsAug 8, 2025
    How to fix 'NO FLOW ON ZONE (0800)' on Bacharach HGM-MZ Measuring Instruments?
    • J
      Jennifer BradleyAug 8, 2025
      If your Bacharach Measuring Instruments are showing 'NO FLOW ON ZONE (0800)', check for a blockage in the air sample line or at the line end filter. Also, inspect the air sample line for kinks or pinch points.
  • L
    Lori ScottAug 13, 2025
    What causes 'LOOP FAULT (0010)' in Bacharach HGM-MZ?
    • J
      Jeanne HendersonAug 13, 2025
      A 'LOOP FAULT (0010)' on your Bacharach Measuring Instruments means that if the dual 4-20 mA dc option card is installed, one or both current loops are open. Check the wiring to the load/monitoring circuit on both 4-20 mA loops to ensure connections, or install shorting jumpers.
  • D
    Debra WagnerAug 17, 2025
    What does 'CONFIG FAULT (0080)' mean on Bacharach Measuring Instruments?
    • A
      Angela GarrettAug 17, 2025
      A 'CONFIG FAULT (0080)' in Bacharach Measuring Instruments indicates an error in the HGM Setup Screen within the Number Zones Installed field.
  • M
    Mathew DicksonAug 21, 2025
    What to do if Bacharach HGM-MZ show 'OVER RANGE DETECTED (2000)'?
    • J
      jessefordAug 21, 2025
      If your Bacharach Measuring Instruments display 'OVER RANGE DETECTED (2000)', it means the measured concentration on one or more zones exceeds the measurement range. Check if the monitor has been exposed to pure refrigerant. If not, check the sensor voltage range.

Summary

Routine Annual Maintenance and Operating Parameter Verification

Detector Voltage and Reference Voltage Adjustment

Procedure for adjusting detector and reference voltages for accurate readings.

System Setup for Voltage Adjustment

Accessing system setup and digipot screens for voltage adjustments.

HGM-MZ Sample Pump Flow Testing

Pump Troubleshooting Tips

Guidance on diagnosing pump issues using pressure and vacuum readings.

HGM-MZ Major Parts List

Filters

Details on charcoal filter assembly and fittings for the HGM-MZ unit.

Maintenance Check List

Bump Gas Testing Procedure

Steps for performing gas tests to ensure proper monitor operation and alarms.

Troubleshooting Guide

Deciphering Fault Codes

Understanding HGM MZ faults and numeric codes for problem diagnosis.

Specific Fault Code Analysis

Analysis of common fault codes like ZERO FILTER, GAIN SET, LOOP, CONFIG.