3-7
Operation & Maintenance Manual
Doc Ref. MN3300RM2 Rev. 5
MANAGEMENT SETTINGS SAMM SETTINGS
Within this menu, you can change the settings of each SAMM to suit your requirements.
Use the buttons to highlight the desired SAMM. The buttons are used to move between
pages. Pressing when at the bottom of the list (or when at the top of the list) will also cause the
display to show the following (or preceding) page of SAMMs. Pressing the button on a highlighted
SAMM displays the intermediate configuration screen, as follows (Note: if the selected SAMM has
been disabled, the intermediate configuration screen will not be shown):
Highlighting Alarm Inhibit and pressing the button will prevent the chosen SAMM from activating a
relay upon an alarm or fault condition. The inhibit remains in place for a maximum of 12 hours, after
which the SAMM returns to the enabled state. The inhibited state can be cancelled at any time by
selecting ‘Alarm Enable’. Whilst inhibited, the SAMM will continue to sample as normal and both the
display and the log files will continue to show the measured PPM and any threshold/fault conditions.
An inhibited SAMM is indicated by the presence ofInhibited’ alongside the SAMM number text at the
top of the screen, also a ‘*’ prefix character will be shown against the SAMM in the SAMMs list
screen. Highlighting ‘Configure’ and pressing the button will confirm the alarm selection and
continue to the configuration screen where the SAMM settings can be edited.
SAMM L3 (Disabled)
Compressor 3
¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯
SAMM Gas Alert Alarm Critical
A1 R134A 20 40 60
A2 R22 22 40 60
L3 R407A 100 300 850
L4 R134A 20 40 60
L5 R134A 20 40 60
L6 R134A 20 40 60
L7 R134A 20 40 60
A8 R134A 20 40 60
< Back Next page >
SAMM L3
Compressor 3
Alarm Inhibit
Alarm Enable
Configure
< Back
SAMM 3 CONFIGURATION
Compressor 3
State: Disabled
Name: Compressor 3
Gas Type: R407A
Freeway Length: 00024 ft
Sampling Mode: Leak
Alert: 00100 ppm
Alarm: 00300 ppm
Critical: 00850 ppm
CANCEL SAVE