MANAGEMENT – SETTINGS – SAMM SETTINGS
Within this menu, you can change the settings of each SAMM to suit your requirements.
Use the buttons to highlight the desired SAMM. The buttons are used to move between
pages. Pressing when at the bottom of the list (or when at the top of the list) will also cause the
display to show the following (or preceding) page of SAMMs. Pressing the button on a highlighted
SAMM displays the intermediate configuration screen, as follows (Note: if the selected SAMM has
been disabled, the intermediate configuration screen will not be shown):
Highlighting ‘Alarm Inhibit’ and pressing the button will prevent the chosen SAMM from activating a
relay upon an alarm or fault condition. The inhibit remains in place for a maximum of 12 hours, after
which the SAMM returns to the enabled state. The inhibited state can be cancelled at any time by
selecting ‘Alarm Enable’. Whilst inhibited, the SAMM will continue to sample as normal and both the
display and the log files will continue to show the measured PPM and any threshold/fault conditions.
An inhibited SAMM is indicated by the presence of ‘Inhibited’ alongside the SAMM number text at the
top of the screen, also a ‘*’ prefix character will be shown against the SAMM in the SAMMs list
screen. Highlighting ‘Configure’ and pressing the button will confirm the alarm selection and
continue to the configuration screen where the SAMM settings can be edited.