Do you have a question about the Balboa 300F Series and is the answer not in the manual?
Spa enters Priming Mode (Pr) when energized. Lasts less than 5 minutes. Press 'Temp' to exit.
Spa shut down due to high temperature. Remove cover, allow to cool, reset.
Spa shut down due to sensor issues. Contact dealer if problem persists.
Errors indicate flow problems or sensor imbalance. Follow action for HL message.
Warning! Shock Hazard! Do not attempt service. Contact dealer for assistance.
This document describes the operation of the Balboa 300F-Series control system for spas, specifically for systems running software v41 and utilizing Balboa Panels VL200 through VL406.
The system begins in Priming Mode (Pr) upon energization. During this mode, which lasts less than 5 minutes, users should repeatedly press the "Jets" button to ensure the pump is free of air. To exit Priming Mode, press "Temp." After priming, the spa will transition to Standard Mode. Some panels may use "Set," "Warm," or "Cool" buttons instead of "Temp."
Temperature Control allows users to set the spa's water temperature between 80°F (26°C) and 104°F (40°C). The current water temperature is continuously displayed, but it is only accurate after the pump has been running for at least 1 minute.
The Jets button controls the spa's pump. Pressing "Jets" turns the pump on or off and switches between low and high speeds (if available). If left running, the pump will automatically turn off after a preset time, which can be up to 2 hours for low speed on some systems. Low speed may operate automatically at times and cannot be deactivated from the panel, though high speed can still be used. The ozone generator (if installed) activates whenever the low speed is running.
The Light button operates the spa light, which automatically turns off after 4 hours.
The Mode of operation can be changed, though this feature may be locked in Standard Mode depending on the system configuration. Mode is changed by pressing "Temp," then "Light."
Preset Filter Cycles are pre-programmed to ensure water quality. The first filter cycle begins 6 minutes after the spa is energized, and the second begins 12 hours later. The filter duration is programmable from 1 to 8 hours, with a default of 1 hour. To program, press "Temp," then "Jets," then "Temp" to adjust, and "Jets" to exit.
Automatic polling (in Standard Mode only) ensures the spa's temperature is regularly checked. The pump will activate for 1 minute to check the temperature:
The system also provides Diagnostic Messages to inform users of potential issues:
Maintenance features are primarily related to addressing diagnostic messages. For example, ensuring pumps are primed for flow issues or allowing the spa to cool for overheat conditions. The system is designed with automatic freeze protection, activating equipment as needed.
Important Safety Warning: This control system contains no user-serviceable parts. Do not attempt service. Contact your dealer or service organization for assistance. All power connection instructions in the owner's manual must be followed, and installation must be performed by a licensed electrician with proper grounding connections.
| Model | 300F Series |
|---|---|
| Frequency | 50/60 Hz |
| Type | Spa Control System |
| Power Supply | 120/240VAC |
| Number of Circuits/Pumps Supported | 2 |
| Temperature Range | 50°F - 104°F |
Loading...