Configuring the MES1A/B
Manual Documentation Number: MES1A/MES1B-2106m PN7138-rev001
B&B Electronics Mfg Co Inc – 707 Dayton Rd - PO Box 1040 - Ottawa IL 61350 - Ph 815-433-5100 - Fax 815-433-5104 – www.bb-elec.com
B&B Electronics Ltd – Westlink Commercial Park – Oranmore, Galway, Ireland – Ph +353 91-792444 – Fax +353 91-792445 – www.bb-europe.com
27
30. To accept changes, press Enter
When RS-422/485 four-wire operation is selected:
When RS-422/485 four-wire operation is selected the RS-422/485 switch
on the MES1B must be in the left position.
When RS-485 two-wire operation is selected:
CP1 (configured in the next section under Modem/Configurable Pin
Settings) must be enabled to ensure Send Data control is implemented.
The RS-422/485 switch on the MES1B must be in the right position.
The multidrop bus is connected to Terminals 3 [DataB(+) to TDB(+)
terminal] and 4 [DataA(-) to TDA(-) terminal].
No jumpers are required to bridge transmit and receive lines on the
terminal block
Serial Parameters
MES1A/B Serial Parameters must be set up to match the parameters of the
Modbus device connected to its serial interface. MES1A/B Serial Parameter
options include:
Data rates from 300 bps to 115200 bps
7 or 8 data bits
No, Even or Odd parity
1 or 2 stop bits.
To configure Serial Parameters:
31. At the
Enter serial parameters (9600,8,N,1)prompt
o To keep the current setting, press Enter
o To change the serial parameters, type in new parameters in the
format
9600,8,N,1
32. To accept changes, press Enter
3) Modem/Configurable Pin Settings
There is only one configurable setting required in the Modem/Configurable
Pin Settings section of the Configuration Menu. When configuring an