9170600990 Rev H BE1-27/59 Testing 5-5
RESULT: The timer displays a response time, dependent on timing type, as indicated in Column 1 of
Table 5-3.
Step 5. Press and release S2. Set the time delay control for the function being tested to 99 (9.9
se
conds). Reset the timer. Press and release S1.
RESULT: The timer displays a response time, dependent on timing type, as indicated in Column 2 of
Table 5
-3.
Step 6. Repeat Steps 1 through 5, as necessa
ry, for each function’s time delay control.
This concludes the operational test procedure.