DGC-2020HD Troubleshooting
Baseload Setpt: This displays the active baseload setpoint.
Peak Shv Setpt: This displays the active peak shave setpoint.
Im/Ex Setpt: This displays the active import/export setpoint.
VRM Control
This screen is useful for debugging VRM-2020 control related issues. It gives visibility into the states of
the VRM-2020 regulation modes and limiters in the DGC-2020HD.
The VRM Control diagnostics screen is located on the front panel at Metering > Diagnostics > VRM
Control.
The following parameters are visible on the VRM Control diagnostics screen:
VRM AVR Setpoint: This displays the AVR mode setpoint.
VRM FCR Setpoint: This displays the FCR mode setpoint.
VRM AVR Ref: This displays the final AVR setpoint (reference) after other factors such as raise/lower
biases or an active limiter.
VRM FCR Ref: This displays the final FCR setpoint (reference) after other factors such as raise/lower
biases or an active limiter.
VRM Control Output: This displays the VRM control output (PID) in per unit.
VRM AVR Error: This displays the difference between the AVR reference and the measured voltage
in per unit.
VRM FCR Error: This displays the difference between the FCR reference and the measured current
in per unit.
VRM OEL Reference: This displays the calculated OEL reference in per unit of takeover OEL or
summing point OEL depending on configuration.
VRM OEL Takeover Err: This displays the difference between the takeover OEL reference and the
measured field current in per unit.
VRM OEL Summing Err: This displays the difference between the summing point OEL reference and
the measured field current in per unit.
VRM OEL Summing Bias: This displays the OEL Summing control output (PID) in per unit.
VRM UEL Reference: This displays the calculated UEL reference in per unit.
VRM UEL Error: This displays the difference between the UEL reference and the measured field
current in per unit.
VRM UEL Bias: This displays the UEL control output (PID) in per unit.
VRM Tracking Error: This displays the difference of the inactive mode setpoint in relation to the active
mode setpoint in percent.
EDM Ripple: The exciter diode ripple is reported by the exciter diode monitor (EDM) as the induced
ripple in the exciter field current.