Safety distances Z from electric lines at:
IRrigation = ZR e. g.: with drinking water, ground water (e. g. well) or running
water (e. g. river)
SlurryG = ZG e.g.: with liquid manure or slurry
H = minimum distance between sprinkler upper edge and conductor cable when
crossing beneath an electric line
The safety distance when crossing beneath an electric line, is reached when the distances as per the
below chart are kept. The water beam may touch the conductor cable but it may not be higher than the
conductor cable.
Sprinkler with rubber wheels Sprinkler with skids
Running direction
Pump tanker on rubber wheels Sprinkler jet pipe directed by hand
ATTENTION: DO NOT SPRAY SLURRY ON INSULATORS AND MASTS!
Safety distance Z in m, measured on the ground
Type and operation mode of
the sprinkler
With rubber wheels or directed by hand
With metal or synthetic pipes
With skids or stationary/fixed
With metal cart and metal pipes
Nozzle diameter in mm or flow in m³/h
26 mm ≙ 50 m
3
/h 36 mm ≙ 100 m
3
/h 26 mm ≙ 50 m
3
/h 36 mm ≙ 100 m
3
/h
Jet type Spray Full Spray Full Spray Full Spray Full
Up to 1.000 V
H = 1 m
ZR 1 5 1 5 1 5 1 5
ZG 1 8 1 8 1 8 1 8
Up to 30.000 V
H = 2,5 m
ZR 3 9 5 21 3 7 4 9
ZG 5 11 7 23 5 9 6 11
Up to 110.000 V
H = 3 m
ZR 3 12 5 24 3 9 4 15
ZG 5 14 7 26 5 11 6 17
Up to 220.000 V
H = 4 m
ZR 4 14 6 26 4 12 6 22
ZG 6 16 8 28 6 14 8 24
Up to 380.000 V
H = 5 m
ZR 5 16 7 26 5 14 6 22
ZG 7 18 9 28 7 16 8 24