6 Settings
Tab.10 Settings table with eMO Life
Name Description
Factory
value
Mini
mum
Maxi
mum
Level
CP060
Required ambient temperature (°C) in the zone in the holiday/anti
freeze period
6 5 20 User
CP070
Maximum ambient setpoint temperature (°C) in reduced mode that
enables switching to comfort mode with climate control (with outside
sensor)
16 5 30 User
CP080 Temperature (°C) set by SLEEP activity in the zone 16 5 30 User
CP081 Temperature (°C) set by HOME activity in the zone 20 5 30 User
CP082 Temperature (°C) set by AWAY activity in the zone 6 5 30 User
CP083 Temperature (°C) set by MORNING activity in the zone 21 5 30 User
CP084 Temperature (°C) set by EVENING activity in the zone 22 5 30 User
CP085 Temperature (°C) set by CUSTOM activity in the zone 20 5 30 User
CP200 Required ambient temperature (°C) for the zone in manual mode 20 5 30 User
CP250 Correct the temperature measured by the room unit 0 -5 +5 User
CP320
Zone operating mode
0: Scheduling
1: Manual
2: Off
0
User
CP510 Temporary room setpoint per zone 20 5 30 User
CP550
Fireplace mode
0: Disabled
1: Enabled
0 User
CP570
Timer programme selected by User
0: Program 1
1: Program 2
2: Program 3
0 User
DP060
Timer programme selected for DHW
0: Program 1
1: Program 2
2: Program 3
0 User
DP080 Reduced temperature setpoint for the domestic hot water tank [°C] 35 10 60 User
DP337 Domestic hot water temperature setpoint for the holiday period [°C] 10 10 60 User
Important
The factory values of some parameters may differ according to
the target market of the product.
400 Combi 2 17