(F) Alarm re-set- Here, the alarm is re-set. If there is no alarm, use the button to come into the set-up
menu (but simultaneously with the (C)-button). The following are the alarms which can
appear:
A-1
There is no fire! The smoke temperature has been below 100°C during operation for
more than 30 minutes of operation, or after intermittent firing and starting up. Check the
smoke gas sensor and remove any coating.
A-2
The ebullition thermostat (D) is switched off. This can be reconnected by pressing when
the cover is removed. (Situated in the boiler's operation panel). The circuit breaker on
the back of the control panel (see 4.2 - electrical diagram) has blown.
A-3
The motor protection for the worm conveyor/auger has failed. This can be reconnected
when the motor is no longer over-burdened.
A-4
The flow temperature has exceeded 94°C.
A-5
Error during communication with the more sensitive parts of the control, i.e. the
program cannot be saved or read.
The programming situation arises when the ON/OFF button (E) has been switched off
by keeping the alarm re-set (F) and the operation form (C) buttons pressed down for
3 seconds. Then 3 horizontal lines will appear in the display and it will be ready for
programming.
Programming -
By "stepping" with the menu key, the data which have been set can be seen.