Commissioning
Name Type Description Default value
TurnUPSOffEnable REG_DWORD Activates/deactivates the switching-off of the
UPS output voltage after the shutdown:
• 0 := deactivated;
• 1 := activated (switches off);
• other values are not permissible;
1
TurnUPSOffWait REG_DWORD Maximum delay time in seconds for switching
off the UPS output voltage after initiating the
Windows shutdown. The permissible values
can differ from model to model (depending on
hardware).
180
BatteryReplaceNoti
fyEnable
REG_DWORD Activates/deactivates the logging of the battery
change service interval warnings in the
Windows event log: UPS software v3.0.0.8
and higher.
0
BatteryReplaceNoti
fyWait
REG_DWORD Delay time in months for the first battery
change warning. This element can adopt a
value of between 0 and 480 months. Other
values are not permissible. Implemented in the
UPS software v3.0.0.8 and higher.
60
Advanced Settings
KEY_LOCAL_MACHINE\SYSTEM\CurrentControlSet\Services\UPS
Name Type Description Default value
FirstMessageDelay REG_DWORD Delay time in seconds for the first power-
fail message to the user
5
MessageInterval REG_DWORD Delay time in seconds for further power-
fail messages to the user.
20
CX2100-09x466 Version: 1.3