EasyManua.ls Logo

Beckhoff EK1101 - Page 19

Beckhoff EK1101
85 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Product overview
EK110x, EK15xx 19Version: 3.6
2.2.2.3 EK1101, EK1101-0080 - Technical data
Technical data EK1101 EK1101-0080
Task within the EtherCAT system Coupling of EtherCAT Terminals
(ELxxxx) to 100BASE-TX
EtherCAT networks
Coupling of EtherCAT Terminals
(ELxxxx) to 100BASE-TX
EtherCAT networks,
Fast Hot Connect technology
Number of EtherCAT Terminals up to 65535 in the overall system
Number of peripheral signals max. 4.2GB addressable IO points
Transmission medium at least Ethernet CAT-5 cable
Cable length between two Bus
Couplers
max. 100m (100BASE-TX)
Protocol / Baud rate EtherCAT Device Protocol / 100MBaud
HotConnect max. number of configurable IDs: 4096
Delay typical 1µs
Bus connection 2 x RJ45
Power supply 24V
DC
(-15%/+20%)
Current consumption 70mA + (E-bus current)/4
E-bus power supply (5 V)
depending on ambient temperature
(at higher current consumption the
EL9410 power feed terminal can be
used in addition)
max. 2000mA (-25°C ... +55°C)
max. 1000mA (> +55°C)
Power contacts max. 24V
DC
, max. 10A
Electrical isolation 500V (power contact/supply voltage/EtherCAT)
Dimensions (W x H x D) approx. 44mm x 100mm x 68mm
Weight approx. 105g
Permissible ambient temperature
range during operation
-25°C ... +60°C
Permissible ambient temperature
range during storage
-40°C ... + 85°C
Permissible relative humidity 95%, no condensation
Mounting [}37]
on 35mm mounting rail conforms to EN 60715
Vibration/shock resistance conforms to EN 60068-2-6 / EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2 / EN 61000-6-4
Protection class IP20
Installation position variable
Approval CE
ATEX [}54]
cULus [}52]
2.2.2.4 Notes re. EtherCAT Fast Hot Connect technology
EtherCAT components that support Fast Hot Connect enable a faster fieldbus boot up following the
establishment of a connection. The boot up depends in detail on the number of devices, the topology and
activated Distributed Clocks. Whereas the normal establishment of a connection and communication takes
several seconds, less than 1 second is possible with FHC components.
Properties and system behavior
Fast Hot Connect is supported from TwinCAT 2.11R3 Build 2221.
Fast Hot Connect ports are specially marked.