EasyManuals Logo

Beckhoff EK1101 User Manual

Beckhoff EK1101
85 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #48 background imageLoading...
Page #48 background image
Mounting and wiring
EK110x, EK15xx48 Version: 3.6
For connecting EtherCAT devices only shielded Ethernet cables that meet the requirements of at least
category 5 (CAT5) according to EN 50173 or ISO/IEC 11801 should be used.
Note
Recommendations about cabling
You may get detailed recommendations about cabling EtherCAT from the documentation
"Recommendations for the design of the infrastructure for EtherCAT/Ethernet", that is avail-
able for download at www.Beckhoff.com.
EtherCAT uses 4 wires for signal transfer.
Due to automatic cable detection (auto-crossing) symmetric (1:1) or cross-over cables can be used between
EtherCAT devices from Beckhoff.
M8 Connector pin assignment
Signal Description Pin (M8)
Tx+ Transmit Data+ 1
Tx- Transmit Data- 4
Rx+ Receive Data+ 2
Rx- Receive Data- 3
Shield Shielding Housing

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Beckhoff EK1101 and is the answer not in the manual?

Beckhoff EK1101 Specifications

General IconGeneral
BrandBeckhoff
ModelEK1101
CategoryI/O Systems
LanguageEnglish

Related product manuals