Operation
EL1904 41Version: 3.0.0
5.4.4 Address settings on TwinSAFE terminals with 65535
possible addresses
Fig.21: Address settings on TwinSAFE terminals with 65535 possible addresses
Set the TwinSAFE address for the terminal using the two dip switches (with 8 setting options) on the left-
hand side of the EL1904 TwinSAFE terminal. TwinSAFE addresses between 1 and 65535 are available.
DIP switches Ad-
dress
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
ON OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF 1
OFF ON OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF 2
ON ON OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF 3
OFF OFF ON OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF 4
ON OFF ON OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF 5
OFF ON ON OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF 6
ON ON ON OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF 7
OFF OFF OFF ON OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF 8
ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON 65535
WARNING
TwinSAFE address
Each TwinSAFE address may only be used once within a network!
The address 0 is not a valid TwinSAFE address!