Functions with basic values (conventional mode)
Override control with AC 24 V with relay contacts Override control with AC 24 V with rotary switch
abc
0%
ZS 50%
100%
Y
ab
c
~
T
Y (DC 0...10 V)
e.g. 1N 4007
1235
YU
~
T
e.g. 1N 4007
1235
YU
0%
ZS 50%
100%
Y
(DC 0...10 V)
Control remotely 0...100% with
positioner SG..
Minimum limit with positioner SG..
1235
YU
–
+
SGA24
SGF24
SGE24
Y
Z
1234
–
+
T
~
1235
YU
SGA24
SGF24
SGE24
Y
Z
1234
Y (DC 0...10 V)
100
0
Y [
V
]
10
min
0
[
%
–
+
T
~
–
+
T
~
Follow-up control (position-dependent) Control with 4...20 mA via external resistor
1 32 5
–
+
1 32 5
Y
U
DC (0)2…10
DC 2…10 V
YU YU
U
1 32 5
4…20
mA
DC 2…10
V
500 Ω
(
+
)
(–)
U
Y
–
+
T
~
Caution:
The operating range must be set to
DC 2...10 V.
The 500 Ω resistor converts the
4...20 mA current signal to a voltage
signal DC 2...10 V
Functional check
1 32 5
–
+
T
~
U
Y
Procedure
1. Apply 24 V to connection 1 and 2
2. Disconnect connection 3:
- with upwards direction of motion:
closing point at top
- with downwards direction of
motion: closing point at bottom
3. Short circuit connections 2 and 3:
- Actuator runs in the opposite
direction
NV24A-MP-TPC
Globe valve actuator, modulating, communicative, AC/
DC 24 V, 1000 N
Functions
NV24A-MP-TPC • en-gb • 2020-01-22 • subject to changes