Technical data
Supply voltage
RCM410R-24
Supply voltage U
s
....................................................................DC 24 V
Tolerance U
s
...................................................................-30…+25 %
Power consumption ..................................................................≤ 2 W
RCM410R-2
Supply voltage U
s
............................ AC/DC 100…240 V (47…63 Hz)
Tolerance U
s
............................................................................. ±15 %
Power consumption .................................................≤ 2 W / ≤ 3.5 VA
Measuring circuit
Measuring current transf. type ...........................................................
..............................................CTAC…, W…, WF…*, WR…, WS…
* Can only be used when CT connection monitoring is disabled on the
RCM410R.
Load .............................................................................................33 Ω
Operating characteristics ..........................................................Type A
Rated voltage U
n
..........see datasheet measuring current transformer
Frequency range .............................................................. 42…70 Hz)
Measuring range RMS ..................................................... 2 mA…50 A
Residual operating current I
Δn
......................................10 mA…30 A
Operating uncertainty ................................... ±10 % (at 0.5…5 x I
Δn
)
Relative uncertainty .......................................................... 0…–20 %
Contact data acc. to IEC 60947-5-1:
Utilisation category ..................AC 13 / AC 14 / DC-12 / DC-12 / DC-12
Rated op. voltage ........................ 230 V / 230 V / 24 V / 110 V / 220 V
Rated op. current. ...................................5 A / 3 A / 1 A / 0.2 A / 0.1 A
Minimum contact rating ................................1 mA at AC/DC ≥ 10 V *
* refers to relays that have not been operated with high contact currents.
Connection
Connection type ......................................................................push-in
Connection properties
rigid ................................................... 0.2…1.5 mm² (AWG 24…16)
flexible without ferrule ...................... 0.2…1.5 mm² (AWG 24…16)
flexible with ferrule and plastic ferrule ......................0.2…0.75 mm²
flexible with ferrule without plastic ferrule .............0.2…1.5 mm² *
* > 0.75 mm² use crimping pliers simlar CRIMPFOX 6 / Weidmüller PZ6/PZ6/5
only.
Technische Daten
Versorgungsspannung
RCM410R-24:
Versorgungsspannung U
s
........................................................DC 24 V
Toleranz von U
s
..............................................................-30…+25 %
Eigenverbrauch .........................................................................≤ 2 W
RCM410R-2:
Versorgungsspannung U
s
................ AC/DC 100…240 V (47…63 Hz)
Toleranz von U
s
........................................................................±15 %
Eigenverbrauch ....................................................... ≤ 2 W / ≤ 3,5 VA
Messkreis
Messstromwandlertyp ........................................................................
..............................................CTAC…, W…, WF…*, WR…, WS…
* Einsatz nur bei deaktivierter Messstromwandler-Anschlussüberwachung am
RCM410R möglich.
Bürde ........................................................................................... 33 Ω
Ansprech-Charakteristik ............................................................. Typ A
Bemessungsspannung U
n
...........siehe Datenblatt Messstromwandler
Frequenzbereich ............................................................... 42…70 Hz
Messbereich RMS ............................................................2 mA…50 A
Ansprechdifferenzstrom I
Δn
...........................................10 mA…30 A
Betriebsmessabweichung ........................... ±10 % (bei 0,5…5 x I
Δn
)
Prozentuale Ansprechunsicherheit ................................... 0…–20 %
Kontaktdaten nach IEC 60947-5-1:
Gebrauchskategorie .................AC 13 / AC 14 / DC-12 / DC-12 / DC-12
Bem.betriebsspannung ............... 230 V / 230 V / 24 V / 110 V / 220 V
Bem.betriebsstrom .................................5 A / 3 A / 1 A / 0,2 A / 0,1 A
Min. Kontaktbelastbarkeit ...........................1 mA bei AC/DC ≥ 10 V *
* bezieht sich auf Relais, die noch nicht mit hohen Kontaktströmen betrieben
wurden
Anschluss
Anschlussart ............................................................................Push-In
Anschlussvermögen
starr .................................................. 0,2…1,5 mm² (AWG 24…16)
flexibel ohne Aderendhülse ............... 0,2…1,5 mm² (AWG 24…16)
flexibel mit Aderendhülse und Plastikhülse ............... 0,2…0,75 mm²
flexibel mit Aderendhülse ohne Plastikhülse ............ 0,2…1,5 mm² *
* > 0,75 mm² nur Crimpzange ähnlich CRIMPFOX 6 / Weidmüller PZ6/PZ6/5
verwenden.
LINETRAXX® RCM410R-24/-2
Alle Rechte vorbehalten.
Nachdruck und Vervielfältigung
nur mit Genehmigung des Herausgebers.
Bender GmbH & Co. KG
Postfach 1161 • 35301 Grünberg • Deutschland
Londorfer Str. 65 • 35305 Grünberg • Deutschland
Tel.: +49 6401 807-0 • Fax: +49 6401 807-259
E-Mail: info@bender.de • www.bender.de
All rights reserved.
Reprinting and duplicating
only with permission of the publisher.
Bender GmbH & Co. KG
PO Box 1161 • 35301 Grünberg • Germany
Londorfer Str. 65 • 35305 Grünberg • Germany
Tel.: +49 6401 807-0 • Fax: +49 6401 807-259
E-Mail: info@bender.de • www.bender.de