TERMINAL BLOCK M3
ANT-SHIELD Antenna
Connection for the antenna of the built in receiver (ANT-signal/SHIELD-shield).
In case of use of an external antenna it is necessary to remove the pre-cabled cable from the terminal ANT
AUX Auxiliary output AUX 1 Output with N.O. contact configurable by means of the logic AUX 1
24V 24 Vdc Accessory power supply 24Vdc 500 mA maximum
MOT Motor Motor connection: 24Vdc.
TERMINAL MENC
ABS ENC Encoder input Absolute encoder input, pre-cabled by factory.
11) PROGRAMMING
The programming of the various functions of the control unit is carried out using the LCD display on the control unit and setting the desired values in
the programming menus described below.
The parameters menu allows you to assign a numerical value to a function, in the same way as a regulating trimmer.
The logic menu allows you to activate or deactivate a function, in the same way as setting a dip-switch.
11.1) TO ACCESS PROGRAMMING
1 -Press the <PG> button to enter the first Installation menu “INST”.
2 -Choose with <+> or <-> button the menu you want to select
3 - Press the button <PG>, the display shows the first function available on the menu.
4 - With the <+> or <-> button, select the function you want.
5 - Press the button <PG>, the display shows the value currently set for the function selected.
6 - With the <+> or <-> button, select the value you intend to assign to the function.
7 - Press the button <PG>, the display shows the signal “PRG” which indicates that programming has been completed.
11.2) PROGRAMMING NOTES
Simultaneously pressing <+> and <-> from inside a function menu allows you to return to the previous menu without making any changes. Hold down
the <+> key or the <-> key to accelerate the increase/decrease of the values.
Hold down the <+> key or the <-> key to accelerate the increase/decrease of the values.
After waiting 120s the control unit quits programming mode and switches off the display.
When the board is switched on, the software version is displayed for around 5 sec
The pre-set logic functions and parameters are made taking account of a typical installation.
12) PARAMETERS, LOGICS AND SPECIAL FUNCTIONS
The following tables describe the functions available on the control unit
12.1) INSTALLATION (inst)
MENU FUNCTION MIN-MAX-(Default) MEMO
BOOM
Select the length of the boom installed on the barrier.
Value expressed in meter from 3m to 5m (all LADY models) or from 7m to 8m (other models)
According to the selected boom length, the optimal value of speed will be set.
3/5 -7/8 (7-8)
Pos
Set the closing direction of the barrier.
The symbol 0--- indicates right barrier (R/RIGHT) DEFAULT
The symbol ---0 indicates left barrier (L/LEFT)
Verify the opening direction of the boom and in case reverse it. Every change of this func-
tion automatically implies the starting of a new AUTOSET procedure.
LADY - RIGHT
(STANDARD)
LADY - LEFT
0--- = RIGHT
---0 = LEFT
( RIGHT )
12.2) PARAMETERS (PAR)
MENU FUNCTION MIN-MAX-(Default) MEMO
TCA
Automatic closing time. Enabled only with logic “TCA”=ON.
At the end of the set time, the control unit commands a closing maneuver .
1-240-(20s)
FSTS
Adjusts the opening and closing speed of the barrier (standard speed, before the slowdown
phase).
50-99-(99)
sldo
Adjusts the slowdown speed of the barrier during the opening phase* (Fig.9 -slow Open). 20-70-(50)
sldc
Adjusts the slowdown speed of the barrier during the closing phase * (Fig.10 -slow Close). 20-70-(50)
tsmo
Sets the starting point of the slowdown during the opening phase (Fig.9- beginning of the slow
Open). The value is expressed in percentage on the entire stroke.
1-99-(20)
tsmc
Sets the starting point of the slowdown during the closing phase (Fig.10- beginning of the slow
Close). The value is expressed in percentage on the entire stroke.
1-99-(20)