Service and Installation Manual
10
Defrost type
0:Electric heating defrost
1:Hot gas defrost
0
0
/
Fan running mode
0:Fan and compressor run or stop
synchronically 1:Fan
runs continuously, stops during
defrost
2: Fan runs continuously, stops
during defrost and defrost dripping
3: Fan runs continuously, stops
during defrost, fan time delay after
defrost
4:Controlled by defrost sensor, fan
stops during defrost.
1
1
/
Fan initial start time delay after
electrified
060
0
0
min
Fan start time delay after defrost
060 , 0: Fan time delay canceled
2
2
min
Fan working lowest temp.
-50℃~Fan working highest temp.
-58
-58
/
-58℉~Fan working highest temp.
Fan working highest temp.
Fan working lowest temp.85
185
185
/
Fan working lowest temp.185
Compressor run and stop in a
proportional time after cabinet sensor
failure
0: Cancel the mode of “Run/stop in a
proportional time”
1: Start the mode of “Run/stop in a
proportional time”
1
1
/
Compressor stop time in the mode of
“Run/stop in a proportional time”
160
5
5
min
Compressor running time in the mode
of “Run/stop in a proportional time”
160
30
30
min
Buzzer alarm output switch
0: Buzzer output disabled
1: Buzzer output enabled
1
1
/
Cabinet temperature lower limit alarm
value
-50Cabinet temperature upper
limit alarm value
-58
-58
/
-58Cabinet temperature upper
limit alarm value
Cabinet temperature upper limit alarm
value
Cabinet temperature lower limit
alarm value85
185
185
/
Cabinet temperature lower limit
alarm value185
Cabinet over temperature alarm time
delay
060
20
20
3min
The initial cabinet over temperature
alarm time delay after electrified
060
40
40
3min
Over temperature alarm upper
deviation
1℃~30
10
10
/
1℉~60
Over temperature alarm lower
deviation
1℃~30
5
5
/
1℉~60
Over temperature alarm mode
0: Absolute temperature point
1:set value+ over temperature alarm
deviation
0
0
/
Light/Alarm relay selection
0:Light output
1:Alarm output
0
0
/