INTELLIBUS
Number : NR 1157
Revision : B
Page 17/19
Instructions for start-up
10 Local stop also
inhibited with a local
command inhibit
0: no, local stop is possible
1: yes, local stop and off inhibited
1
read / write
11 Dead band for
positioner function
Unit 0.1%
mini value: 2 (0.2%)
maxi value: 50 (5%)
1
read / write
12 Timing control 0: no timing control
1: timing control
1
read / write
13 Start of closing
temporised zone
0 to100 % 1
read / write
14 End of closing
temporised zone
0 to 100 % (lower than start value) 1
read / write
15 Start of opening
temporised zone
0 to100 % 1
read / write
16 End of opening
temporised zone
0 to 100 % (higher than start value) 1
read / write
17 Timer open time
expected
in seconds 2
read / write
18 Timer close time
expected
in seconds 2
read / write
19 Operating time without
timer
in seconds 2
read / write
20 no local stop in remote
mode
0= local stop possible
1= no local stop
1
read / write
21 Fail safe position in
case of loss of
communication
0= stayput
1= closing
2= opening
1
read / write
22 open priority 0= no priority
1= open priority
1
read / write
23 close priority 0= no priority
1= close priority
1
read / write
24 In case of emergency
command, torque limit
is 100%
0= no
1= yes
1
read / write
25 In case of emergency
command, thermal
overload is by- passed
0= no
1= yes
1
read / write
26 External gear ratio (format: 1/ )
ex 200 = 1/200
2
read only
27 Actuator number ASCII characters 16
read only
28 Manufacture date ASCII characters 12
read only
29 Software version ASCII characters ex:1.03 6
read only
30 Stroke measured
during set-up
For stroke unit see address 7
2
read only
31 Opening torque curve Torque in %
Data 1 = closed position
Data 2= 1% open
Data 101= 100% open
101
read only