INTELLIBUS
Number : NR 1157
Revision : B
Page 16/19
Instructions for start-up
6 TRANSDUCER BLOCK
Available data through FIELDBUS in the Transducer Block
N° Data Value
Number
of bytes
Type
1 Operating class 1: On - Off
2: Modulating Classe III
3 : Modulating Classe II
1
read only
2 Nut thread
(If linear system)
In mm (To calculate the stroke but
only during set-up). Value is zero if
no linear system.
1
read only
3 Locked motor timing In seconds 1
read only
4 Motor supply type 0: 3 phase
1: single phase or DC
1
read only
5 Reverse delay time (unit 50ms)
Ex. 3 = 150ms
1
read only
6 Closing mode 0: close on position
1: close on torque
3: open and close on torque
1
read only
7 Stroke unit 1: number of turns
2: degrees
3: mm
1
read only
8 Set-up for auxiliary
command 1
() Bit state for active
command
(see 4.1)
0: not used
1:local(0)/remote(1)
2:local+remote(0)
/remote(1)
3:local command inhibit(1)
4:open inhibit(1)
5:close inhibit(1)
6:On-off(0) / AUTO(1)
7:fieldbus emergency closing (1)
8: fieldbus emergency opening (1)
9: fieldbus emergency stop (1)
10: partial stroking (1)
1
read / write
9 Set-up for auxiliary
command 2
coming through the
fieldbus but for
emergency commands
wired separately from
the fieldbus.
0: not used
1:local(0)/remote(1)
2:local+remote(0)
/remote(1)
3:local command inhibit(1)
4:open inhibit(1)
5:close inhibit(1)
6:On-off(0) / AUTO(1)
7:wired emergency closing (1)
8: wired emergency opening (1)
9: wired emergency stop (1)
10: partial stroking (1)
1
read / write