INTELLIBUS
Number : NR 1157
Revision : B
Page 18/19
Instructions for start-up
32 Closing torque curve Torque in %
Data 1 = closed position
Data 2= 1% open
Data 101= 100% open
101
read only
33 Open breakout max
torque during the last
electrical actuation
in % 1
read only
34 Close tight max torque
during the last electrical
actuation
in % 1
read only
35 Opening max torque
during the last electrical
actuation
in % 1
read only
36 Closing max torque
during the last electrical
actuation
in % 1
read only
37 Starts last 12 hours 2
read only
38 Total number of starts 4
read only
39 Total running time Unit is 1/10 sec 4
read only
40 Partial number of starts
(since the last reset)
4
read only
41 Partial running time
(since the last reset)
Unit is 1/10 sec 4
read only
42 locked motor open 0= no fault, 1= fault 1
read only
43 locked motor close 0= no fault, 1= fault 1
read only
44 torque sensor 0= no fault, 1= fault 1
read only
44 position sensor 0= no fault, 1= fault 1
read only
46 Closing direction of
rotation discrepant
0= no fault, 1= fault 1
read only
47 Opening direction of
rotation discrepant
0= no fault, 1= fault 1
read only
48 overtravel 0= no fault, 1= fault 1
read only
49 too many starts 0= no fault, 1= fault 1
read only
50 lost phase 0= no fault, 1= fault 1
read only
51 lost signal 0= no fault, 1= fault 1
read only
52 thermal overload 0= no fault, 1= fault 1
read only
53 pumping 0= no fault, 1= fault 1
read only
54 config. memory 0= no fault, 1= fault 1
read only
55 activity memory 0= no fault, 1= fault 1
read only
56 base memory 0= no fault, 1= fault 1
read only
57 24V auxiliary
0= no fault, 1= fault 1
read only
58 User pass word ASCII characters
"000" to "999"
3
read / write
59 Valve tag number ASCII characters
ex: "MOV55VV"
8
read / write
60 Open breakout torque
setting
40 to 100%, 101% if no limitation 1
read / write