INSTALLATION MANUAL
ENGLISH
TABLE “A” PARAMETERS
Any modication of parameters/logics must be conrmed by pressing S2 > 5s
TRIMMER Parameter
+
min.
+
max.
Description
T1
Automatic
closing time [s]
0 120
Waiting time before automatic closing.
NOTE: Set to 0 if not used.
T2 Leaf force [%] 1 100
Force exerted by leaf/leaves.
WARNING: It aects impact force directly: make sure that current safety requirements are met with
the set value (*).
To comply with the current safety regulations, install anti-crushing safety devices (**).
Note: if this parameter is modied, a new Autoset must be carried out.
T3
Slowdown
time [s]
0 30
Sets the slowdown time performed at the end of each opening and closing operation.
0 = Slowdown disabled
NOTE: Do not use with hydraulic motors.
T4
Motor 1 closing
delay time [s]
0 25
Motor 1 closing delay time with respect to motor 2.
NOTE: set 0 for single motor operations (leaf 1).
(*) In the European Union, apply standard EN 12453 for force limitations, and standard EN 12445 for measuring method.
(**) Impact forces must be limited with the use of EN12978 compliant active safety edges
ERROR TABLE:
Led ERR
Lit slow ashing fast ashing
Led SET
Unlit
Photocell test,
Costa o Costa 8k2 failed
- Check photocell connection and/or logic
settings
Lit
Reverse due to
obstacle - Amperostop
- Try turning the board o and back on or
press button S2. If the problem persists, con-
tact the technical assistance department.
Thermal cutout
-
Allow automated device to cool
slow
ashing
Internal system supervision control error.
- Try switching the board o and back on
again.
- If the problem persists, contact the technical
assistance department.
- Thermal overload protection triggered on
one of the 2 motors
Changed settings and/or Operating logics
press S2 for 5s to conrm.
ALENA SW2 CPEM -
25