TABLE “B” LOGICS
Any modication of parameters/logics must be conrmed by pressing S2 > 5s
DIP Logic Default
Cross out
setting used
Description
1
Transmitter
programming
ON
ON
Enables wireless memorizing of transmitters:
1- Press in sequence the hidden key and normal key (T1-T2-T3-T4) of a transmitter that has
already been memorized in standard mode via the radio menu.
2- Press within 10 sec. the hidden key and normal key (T1-T2-T3-T4) of a transmitter to be
memorized.
The receiver exits programming mode after 10 sec.: you can use this time to enter other new
transmitters.
This mode does not require access to the control panel.
IMPORTANT: Enables the automatic addition of new transmitters, clones and replays.
OFF
Disables wireless memorizing of transmitters and automatic addition of clones.
Transmitters are memorized only using the relevant Radio menu or automatically with re-
plays.
IMPORTANT: Disables the automatic addition of new transmitters and clones
2 BAR / 8K2 OFF
ON
Input congured as Bar 8k2 (Fig.G). Input for resistive edge 8K2.
The command reverses movement for 2 sec.
OFF
Input congured as Bar, safety edge (Fig.G).
The command reverses movement for 2 sec..
3
Photocell input
check
OFF
ON Enable safety check on the PHOT input. Fig.G
OFF Safety check on PHOT input not enabled. Fig.G
4 Edge input check OFF
ON Enable safety check on the BAR input. Fig.G
OFF Safety check on BAR input not enabled. Fig.G
5
Photocells
during closing
OFF
ON
In the event beam is broken, photocell operation is disabled during opening. During closing,
movement is reversed immediately.
OFF
When beam is broken, photocells are active during both opening and clo-
sing. When beam is broken during closing, movement is reversed only once the
photocell is cleared.
6
Safety edge input
operation
OFF
ON
Safety edge with active reversal only when closing, when opening the movement stops
OFF
Safety edge with active reversal in both directions
7 Fast closing OFF
ON Closes 3 seconds after the photocells are cleared before waiting for the set TCA to elapse.
OFF Logic not enabled
8
Residential /
apartment
building
operation
OFF
ON
Sets the automation type of operation:
ON = Apartment building
OFF OFF = Residential
Reaction to the START input (wired or radio):
Residential Apartment
building
CLOSED Opens Opens
WHILE CLOSING Stops Opens
OPEN Closes Closes
WHILE OPENING STOPS + TCA No eect
AFTER STOP Opens Opens
Reaction to the OPEN input (wired):
Residential Apartment
building
CLOSED Opens Opens
WHILE CLOSING Opens Opens
OPEN No eect No eect
WHILE OPENING Keeps it open Keeps it open
AFTER STOP Opens Opens
Reaction to the PEDESTRIAN input (radio):
Residential Apartment
building
CLOSED Opens partially Opens partially
WHILE CLOSING Stops Opens partially
OPEN Closes Closes
WHILE OPENING STOPS + TCA No eect
AFTER STOP Opens partially Opens partially
9
Hammer during
opening
OFF
ON
Before opening completely, the gate pushes for approx. 2 seconds as it closes. This allows
the solenoid lock to be released more easily.
IMPORTANT - Do not use this function if suitable mechanical stops are not in place.
OFF
Logic not enabled