6. Appendix
ORM0043_2
Modulating Controller Application Manual
Page 13
6.3 System Values
Feedback Value indicating the actual actuator position based on an analogue signal
Command Signal Value indicating the required command position based on a 4-20mA analogue signal
Remote Command Value indicating a user specified required command position
Open Limit Value indicating the position at which the actuator is deemed to be fully open
Close Limit Value indicating the position at which the actuator is deemed to be fully closed
Open Static DZ Value indicating how much the command signal must be greater than the feedback position,
when the actuator is static, before it starts to open
Open Moving DZ Value indicating how much the feedback signal must be less than the command signal, when
the actuator is opening, before it becomes static
Open Pulse Zone Value indicating how much the feedback signal must be less than the command signal, when
the actuator is opening, before it starts pulsing the open solenoid
Close Static DZ Value indicating how much the command signal must be less than the feedback position, when
the actuator is static, before it starts to close
Close Moving DZ Value indicating how much the feedback signal must be greater than the command signal,
when the actuator is closing, before it becomes static
Close Pulse Zone Value indicating how much the feedback signal must be greater than the command signal,
when the actuator is closing, before it starts pulsing the close solenoid
Accum Pressure Value indicating the accumulator pressure based on an analogue signal
Low Pressure SP Value indicating the pressure at which a low accumulator pressure fault will be raised
Pump Start SP Value indicating the pressure at which the pump starts to run in order to build pressure in the
accumulator
Pump Stop SP Value indicating the pressure at which the pump is stopped due to the correct pressure being
present in the accumulator
High Pressure SP Value indicating the pressure at which a high accumulator pressure fault will be raised
Supply Pressure Value indicating the hydraulic supply pressure based on an analogue signal
Min Supply Px SP Value indicating the pressure at which a low supply pressure fault will be raised