6. Appendix
ORM0043_2
Modulating Controller Application Manual
Page 14
6.4 System Times
Max Manual Time Maximum time the controller can be in manual mode before being returned to automatic
mode
Sig Fault Delay Time an analogue signal has to be in fault before it is registered
Act Limit Delay Time the actuator position has to be above the open limit or below the close limit before it is
registered
Position Delay Time positioning is delayed when requested movement is within two times the actuator dead
zone
Open Limit Move Time that the Open Solenoid pulses active when at the pulse zone limit when the actuator is
opening
Open Blnce Move Time that the Open Solenoid pulses active when at the balance position when the actuator is
opening
Open Limit Pause Time that the Open Solenoid pulses off when at the pulse zone limit when the actuator is
opening
Open Blnce Pause Time that the Open Solenoid pulses off when at the balance position when the actuator is
opening
Close Limit Move Time that the Close Solenoid pulses active when at the pulse zone limit when the actuator is
closing
Close Blnce Move Time that the Close Solenoid pulses active when at the balance position when the actuator is
closing
Clse Limit Pause Time that the Close Solenoid pulses off when at the pulse zone limit when the actuator is
closing
Clse Blnce Pause Time that the Close Solenoid pulses off when at the balance position when the actuator is
closing
Pump Run On Time that the pump runs on after it has run on demand
Pump Run Max Maximum time that the pump can run continuously before it is stopped and an Overrun Fault is
raised
Px Limit Delay Time a pressure set point must be active before it is registered
Lx Limit Delay Time a level switch set point must be active before it is registered
Tx Limit Delay Time a temperature switch set point must be active before it is registered
Supply Px Delay Time the supply pressure set point must be active before it is registered
6.5 HART Variables
Primary Feedback
Secondary Command Signal
Tertiary Accum Pressure
Quaternary N/A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bifold Orange EHPC210 and is the answer not in the manual?

Bifold Orange EHPC210 Specifications

General IconGeneral
ManufacturerBifold
Input Voltage24 VDC
Output Voltage24 VDC
Operating Temperature-20°C to +60°C
Weight0.5 kg
ModelOrange EHPC210