2.7 Exchanging the valve plate / cylinder head gasket
Release pressure in compressor.
Remove cylinder head and valve plate (if necessary with
plastic hammer). Carefully clean all flange surfaces.
Examine valve plate, if damaged exchange complete. Find
and cure cause (see "fault diagnosis").
Fit cylinder head, valve plate and new gasket correctly . In
an unfavorable mounting situation use mounting pins as
assistance.
Attention! Do not oil asbestos free gaskets (danger of
leakage).
Tighten the screws crosswise in the order shown in two
stages (see Fig. 5, tightening torque 60 Nm, from serial
number 467... : 80 Nm).
2.7 Austausch Ventilplatte / Zylinderkopfdichtung
Verdichter in drucklosen Zustand bringen.
Zylinderkopf und Ventilplatte demontieren (ggf. mit Gummi-
hammer lösen). Alle Flanschflächen sorgfältig reinigen.
Ventilplatte prüfen, bei Schäden komplett austauschen.
Ursache ermitteln (siehe „Fehlerdiagnose“) und beseitigen.
Zylinderkopf, Ventilplatte und neue Dichtungen korrekt auf-
setzen. In ungünstiger Einbaulage können Montagestifte
zur Hilfe genommen werden.
Achtung! Asbestfreie Dichtungen dürfen nicht eingeölt
werden (Gefahr von Undichtigkeit).
Schrauben in der dargestellten Reihenfolge über Kreuz in
zwei Stufen anziehen (siehe Abbildung 5, Anzugsmoment
60 Nm, ab Fertigungsnummer 467... : 80 Nm).
Abb. 5 Austausch Ventilplatte / Zylinderkopfdichtung Fig. 5 Exchanging the valve plate / cylinder head gasket
50
12
8,1
10
+0,2
0
+0,1
0
Montagehilfe
Mounting help
1
2
3
4
5
6
7
8
NO OIL!
CR-Zyl.kopf
CR cyl. head