Compressor Control Module CM-RC-01
3.0
26 / 44
9.3 Alarm list
No.
Text
Warning
Critical
Fault
10-*
System - Operation
1000
Too many identical timed reset faults in 24 hours
No
No
Yes
Extern
1001
Too many timed reset faults in 1 hour
No
No
Yes
Extern
12-*
System - Supply
1200
Mains Failure
No
No
Yes
Timed
20-*
Application - Operation
2000
LOCKED
No
No
Yes
Extern
27-*
Application - SW Configuration
2700
Setup Fault
No
No
Yes
Restart
30-*
Compressor - Operation
3001
Envelope: SST Low, SDT Low
Yes
Yes
Yes
Timed
3002
Envelope: SST Low
Yes
Yes
Yes
Timed
3003
Envelope: SST Low, SDT High
Yes
Yes
Yes
Timed
3004
Envelope: SDT High
Yes
Yes
Yes
Timed
3005
Envelope: SST High, SDT High
Yes
Yes
Yes
Timed
3006
Envelope: SST High
Yes
Yes
Yes
Timed
3007
Envelope: SST High, SDT Low
Yes
Yes
Yes
Timed
3008
Envelope: SDT Low
Yes
Yes
Yes
Timed
3010
Envelope: Startup Timeout
No
No
Yes
Timed
3011
Envelope: Configuration Failure
No
No
Yes
Restart
3022
Too Many Compressor Starts
Yes
No
No
N/A
3024
Minimum Compressor Stop Time Not Respected
Yes
No
No
N/A
3025
Minimum Compressor Run Time Not Respected
Yes
No
No
N/A
3026
Minimum Compressor Start To Start Time Not Respected
Yes
No
No
N/A
3027
Compressor Start without being fully unloaded
Yes
No
No
N/A
33-*
Compressor - Temperature
3302
Discharge Temperature High
Yes
Yes
Yes
Timed
3310
Head Fan Cycle Count Per Hour Exceeded
Yes
No
No
N/A
34-*
Compressor - Pressure