EasyManua.ls Logo

Bitzer CM-RC-01

Bitzer CM-RC-01
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
v. 3.0
Reference guide
Compressor Control Module CM-RC-01
3.0
34 / 44
Modbus
type & addr
Name
Possible
values
Default
Description
IR 12027
Motor start is
requested
(Input.StartActive)
unit None
scale 1
uint8
-
Motor start is requested
(0=Off, 1=On)
IR 12028
Head cooling fan
(Output.HeadFan)
unit None
scale 1
uint8
-
Head cooling fan
(0=Off, 1=On)
IR 12029
Liquid injection cooling
valve
(Output.LiquidInject)
unit None
scale 1
uint8
-
Liquid injection cooling valve
(0=Off, 1=On)
IR 12030
Compressor start
unloading valve
(Output.Unloader)
unit None
scale 1
uint8
-
Compressor start unloading valve
(0=Off, 1=On)
IR 12031
Capacity control valve
CR-1
(Output.CapReg1)
unit None
scale 1
uint8
-
Capacity control valve CR-1
(0=Off, 1=On)
IR 12032
Capacity control valve
CR-2
(Output.CapReg2)
unit None
scale 1
uint8
-
Capacity control valve CR-2
(0=Off, 1=On)
IR 12033
Capacity control valve
CR-3
(Output.CapReg3)
unit None
scale 1
uint8
-
Capacity control valve CR-3
(0=Off, 1=On)
10.3.4 Status motor
The group contains status information for the motor.
Modbus
type & addr
Name
Possible
values
Default
Description
IR 13001
Motor overheat
thermistor resistance
(PTC)
(Input.Thermistor)
unit Ohm
scale 1
uint16
-
Motor overheat thermistor resistance (PTC)
IR 13002
Estimated motor
power consumption
(Input.Power)
unit kW
scale 10
uint16
-
Estimated motor power consumption
IR 13003
Motor drive frequency
(speed)
(Input.PhaseFreq)
unit Hz
scale 10
uint16
-
Motor drive frequency (speed)
IR 13006
Motor start contactor
1
(Output.MotorStart1)
unit None
scale 1
uint8
-
Motor start contactor 1
(0=Off, 1=On)
IR 13007
Motor start contactor
2
(Output.MotorStart2)
unit None
scale 1
uint8
-
Motor start contactor 2
(0=Off, 1=On)

Table of Contents