Minimum/Maximum
Supply Pressure “W.C.
7/10
FOR NG AND LP
7/9
FOR NG AND LP
N/A N/A
Nozzle
N/A N/A 2 X 60B 2 X 60B
Pump Pressure
N/A N/A 100/120/150/200 150/200
Head Setting
10.1 4 1 4
Air Setting (Beckett-
Shutter/Band) (Riello Air
Gate)
10/0 3.5 100 PSI 3/1
120 PSI 3/1
150 PSI 2/2
150 PSI 3.4
200 PSI 4.5
NOTE: The above settings are approximations based upon clean equipment in proper working order. Combustion air
adjustments will vary with location, altitude and type of fuel used.
BECKETT CG10-24 (THE BECKETT CG10-24 BURNER IS DESIGNED TO BE USED SOLELY WITH THE
BECKETT 7590 GAS BURNER PRIMARY CONTROL AND THE 7474 GAS IGNITER.
1.) Loosen shutter and band and move to desired settings.
2.) Once desired settings are attained lock in place by tightening back shutter and band screws.
WARNING: LACK OF COMBUSTION AIR CAN CAUSE A DIRTY FIRE, ODOURS IN ENCLOSED
SPACES, AND BACKDRAFTING, POTENTIALLY RESULTING IN NAUSEA OR ASPHYXIATION OF
ALL AIR ADJUSTMENTS MUST BE DONE BY A QUALIFIED SERVICE TECHNICIAN