Blue Sky Energy IPN ProRemote
7 Blue Sky Energy | USA | www.blueskyenergyinc.com
FIGURE 3 - SETUP Menu
From Advanced Display menu
To Battery Charge Parameters menu if selected.
FIGURE 4
SET BAT AMP-HRS
220AH SEL
Total battery amp-hours at 25C, 20hr rate.
SET CHG EFICENCY
94% SEL
SET CHGEFCY MODE
AUTO ADJUST SEL
SET SELF-DISCHG
12%/MONTH SEL
17%/MONTH SEL
+1980AH CLR
Self discharge rate in percent per month at 25C.
SET AUX OUT MODE
BAT VOLTS SEL
-9876543AH CLR
Sets IPN Master charge controller “load control” mode to be based on
battery VOLTS or battery AMP-HOURS. Setting units (V or AH) in setting
screens change based on present mode setting.
--------------
Note: Be certain to set voltage settings even if using amp-hour control as
the charge controller will default to voltage control if battery amp-hours
are unavailable.
SET AUX OUT OFF
<
11.5V SEL
SET BAT CHARGE
PARAMETERS SEL
SET AUX OUT ON
>
12.6V SEL
SET BACK-LIGHT
AUTO SEL
-9876543AH CLR
Enables, disables and sets ON time for lighting control mode. Lighting
control mode is disabled if BOTH Post-Dusk and Pre-Dawn timers are set
to DISABLED (<0.5 hrs). Lighting control mode is enabled if EITHER Post-
Dusk or Pre-Dawn timers are set to a time value. See charge controller
operators manual.
RESTORE DEFAULT
SETINGS SET
-9876543AH CLR
Corrects for “zero offset” in net battery current display.
--------------
CAUTION: Be certain shunt signal is a true zero before performing this
function or inaccurate battery current & amp-hour readings will result.
See Resetting Current Shunt Zero section of manual before proceeding!
With charge efficiency set to 94%, battery is expected to retain 94 amp-
hours for each 100 amp-hours of charge. With charge efficiency mode set
to FIXED, charge efficiency value remains as set. If set to AUTO ADJUST it
automatically adjusts based on actual charge efficiency to continuously
improve remaining battery capacity accuracy.
SET MAXIMUM BAT
VOLTS 15.5V SEL
17%/MONTH SEL
+1980AH CLR
Maximum charge voltage setpoint limit regardless of other settings or
temperature compensation.
RESET CURRENT
SHUNT ZERO SET
-9876543AH CLR
Restores all factory default settings in the IPN ProRemote and charge
controllers, except for auxiliary output settings in slave controllers. Only
the Master’s auxiliary output settings are available over the IPN network
and are restored.
POST-DUSK LIGHTS
ON 2.5 HRS SEL
PRE-DAWN LIGHTS
DISABLED SEL
Sets display backlight to ON, OFF or AUTO. In AUTO, backlight remains ON
for one minute following last key press.