31
We reserve the right to make changes without any prior notice. Translation from original instructions
5.4.4 Connectiontothehotwatercoil
Refer to the dimensional drawings for the position and size of the water connections.
Please observe the following guidelines:
- use copper or steel pipes;
- adequately insulate the pipes;
- install shut-off valves in/out of the unit;
- install a thermometer and a pressure gauge at the input and output of the unit.
Should the uid contained in the hydraulic system be able to fall to near or below zero Celsius, add an appro-
priate percentage of antifreeze.
5.4.5 Connectiontothehumidier
Where present, the humidier must be supplied with untreated mains water, preferably ltered from impurities and / or wa-
ste. The diameters of the couplings are reported in the dimensional drawings.
We recommend that the drain duct should consist of a non-electrically conductive material.
The water discharged from the humidier can reach 100 ° C.
It is compulsory to implement a syphon in order to drain the water from the humidier.
Absolutely do not ll the humidier with demineralised or softened water.
Further information concerning installation may be found in the "Humidier" chapter and in the humidier manual enclosed
with the unit’s documentation.