BL6-U Parallel Integrated Controller Quick Commissioning User Manual
55
5. H-01: Display current running speed (Unit: cm/s):
6. H-02: Hoistway parameter self-learning:
Display L2 when run elevator to lower limit position.
Press ENTER, and elevator perform hoistway auto tuning
automatically. Display current floor.
Display corresponding error code if auto tuning failed.
Press ENTER to quit auto tuning.
Restore display L2 if auto tuning successful.
Please check Appendix III hoistway auto tuning error code
Press ENTER to quit.