B400R 1-3kVA User Manual
33
5.4.5 The control menu
By pressing the button whilst on the menu item “Control”, the display will enter the next menu
tree. The following options are available:
1) Buzzer mute: the buzzer will stop beeping (enter silence mode).
2) Start battery test: commands the UPS to do a battery test.
3) Load segments: commands to control two load segments when the UPS is in output mode.
4) Clear EPO status: once the EPO status is enabled, the UPS output will be cut off. To recover to
normal status, first the EPO connector should be closed, and then enter this menu to clear EPO
status, the UPS alarm will then stop and recover to bypass or standby mode. The UPS needs be
turned on by manual operation.
5) Reset Fault status: when a fault occurs, the UPS will remain in Fault mode and alarm. To recover
to normal status, enter this menu to reset error status, the UPS alarm will then stop and recover to
bypass or standby mode. The reason for the fault should be checked and rectified before the UPS is
turned on again by manual operation.
6) Clear event log: To clear the entire event, alarm and fault history that has been recorded.
7) Restore factory settings: all the settings will be reset to default factory settings. This can only be
done whilst in bypass or standby mode.