Panel event Modem4 code
D6500 mode
Modem4 code
Bosch SIA mode
Contact ID event Contact ID code
SDI Device Tamper Restore TsssD NES Exp. Module Tamper
Restore
3 341 00
1
zzz
SDI Device Trouble TsssD NET System Peripheral Trouble 1 330 00
1
zzz
SDI Device Trouble Restore RsssD NER System Peripheral Trouble
Restore
3 330 00
1
zzz
SDI2 device is missing TsssD NpiddddEM Expansion Module Failure 1 333 00 000
SDI2 device is restored from
missing
RsssD NpiddddEN Expansion Module Failure 3 333 00 000
SDI2 Open Trouble TsssD NpiiddddET Expansion Module Failure 1 333 00
1
zzz
SDI2 Open Trouble Restoral RsssD NpiddddER Expansion Module Failure
Restore
3 333 00
1
zzz
Sensor Reset NsD27 Nriaa/idiiiiXlrrrr Sounder/Relay Reset 3 320 00 000
Service Bypass Npppp NriaaUBpppp Service Request 1 616 aa ppp
Service Bypass Cancel RBpppp NriaaUUpppp Service Request Restore 3 616 aa ppp
Service Smoke Detector Tpppp NriaaASpppp Maintenance Alert 1 393 aa ppp
Service Smoke Detector
Restore
Rpppp NriaaANpppp Maintenance Alert Restore 3 393 aa ppp
Service Walk Test End RsssF NidiiiiTE Service On/Off Premises 3 466 aa uuu
Service Walk Test Start TsssF Nriaa/idiiiiTS Service On/Off Premises 1 466 aa uuu
Sked Changed – No User
Identified
NsD06 NaikkkJS Schedule Change 1 630 00 000
Sked Changed by User NsD06 Nidiiii/aikkkJS Schedule Change 1 630 00 000
Sked has Executed NsD25 NaikkkJR Local Only Local Only
Status: Burg Alarm SApppp OriaaBApppp NA NA
Status: Burg Supervisory STpppp OriaaBSpppp NA NA
Status: Burg Trouble STpppp OriaaBTpppp NA NA
Status: Close by Area SCssss OriaCL NA NA
Status: Fire Alarm SFpppp OriaaFApppp NA NA
Status: Fire Supervisory SEpppp OriaaFSpppp NA NA
Status: Fire Trouble SGpppp OriaaFTpppp NA NA
Status: Gas Alarm SApppp NriaaGAppp NA NA
Status: Gas Supervisory SJpppp NriaaGSppp NA NA
Status: Gas Trouble STpppp NriaaGTppp NA NA
Status: Open by Area SOssss OriaOP NA NA