User ID type Keypad display Contact ID
reporting
Modem format User text
Service User 0 F00 0 “SERVICE USER”
Standard Users 1…50 001…50 1…50 {configured text}
Time Sync 5001 F01 5001 “AUTO TIME SYNC”
RPS User 5002 F02 5002/none “BY RPS”
Automation User 5003 F03 5003/none “BY AUTOMATION”
Keyswitch 5004 F04 5004 “BY KEYSWITCH”
No User Specified User not displayed 000 0xFFFF (displays blank) {no text}
Keypad alarm virtual point numbers (ppp, pppp)
Special point numbers identify the originator of manually created keypad alarm events. All
special point numbers are defined in the table below.
Notice!
The point numbers for manually created keypad alarm events are changed in control panel
firmware version 3.01.
Originating keypad Control panel firmware
version 2.04 and lower,
reported point number
Control panel firmware
version 3.01 and higher,
reported point number
Keypad 1 330 901
Keypad 2 340 902
Keypad 3 350 903
Keypad 4 360 904
Keypad 5 370 905
Keypad 6 380 906
Keypad 7 390 907
Keypad 8 400 908