EasyManua.ls Logo

Bosch D7024 - Page 44

Bosch D7024
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
D7024 | Operation and Installation Guide | 7.0 Control Panel Programming
44 Bosch | 7/05 | 31499J
Local Only
Shortcut:
0-PROG > 4-PROG INPUTS > 2-POINT
FUNCTION
Enabling this feature means the input point gives local
annunciation only, with no Communicator Report.
1. Enter the point number you want to program and
press [#].
The display scrolls through the PROG
FUNCTION options.
2. Press [1] to select LOCAL ONLY and access:
3. Press [1] to enable or [0] to disable.
The preceding window appears.
Silencing
Shortcut: 0-PROG > 4-PROG INPUTS > 2-POINT
FUNCTION
1. Enter the point number you want to program and
press [#].
The display scrolls through the PROG
FUNCTION options.
2. Press [2] to select SILENCEABLE and access:
3. Press [1] to enable or [0] to disable.
The preceding window appears.
FF indicates the function that is being programmed.
Loop Response
Shortcut:
0-PROG > 4-PROG INPUTS > 2-POINT
FUNCTION
This feature allows you to configure points to activate
with standard response time (Setting 1) or with one
system-wide programmed response time (Setting 2).
1. Enter the point number you want to program and
press [#].
The display scrolls through the PROG
FUNCTION options.
2. Press [4] to select LOOP RESPONSE and access:
3. Press the number key corresponding to your
selection.
The current setting appears in parentheses on the
first line. Then the preceding window appears.
When you select a programmed response time, the
system prompts you to enter a time from 1 to 89 sec.
This time is applied to all functions that share a single
programmable response time setting. If the response
time is set for multiple functions, the last time set is used.
When set for fast response operation, multiplex points
have a response time of approximately 1 sec. The
multiplex point response time is the maximum time an
input must be held to guarantee an alarm. Response
time increases as points on the bus are off-normal (in
alarm or with a loop or detector trouble) to a maximum
of 20 sec where all points on the bus are in trouble and
one point is in alarm. On a fully loaded system with
only a few points in alarm or trouble, fast response time
remain at approximately 1 sec. For programmed
response, the response time tolerance is ± 3 sec when
only a few points are off-normal, and increases up to
20 sec when all points are off-normal.
The onboard point response time tolerance is ± 1 sec for
programmed response time, and +0.5 to 0.25 sec for fast
response time.
<DRILL> NEXT FCT: Press [DRILL] to move to the
next function. For example, programming Point
Function 2 and pressing [DRILL] accesses the Point
Function 3 setting.
<HIST> PREV FCT: Press [HISTORY] to return to
the preceding function. For example, programming
Point Function 2 and pressing [HISTORY] accesses the
Point Function 1 setting.
LOCAL ONLY
_ _ _:YES(1)NO(0)
SILENCABLE? (FF)
_ _ _:YES(1)NO(0)
A limit of 20 points can be assigned to point
functions programmed with a response time
other than Fast. If more than 20 points are
assigned to functions programmed with a
response time other than Fast, the error mes-
sage MAX PROGRAMD POINTS EXCEEDED
appears. Changing a point function from Fast
to Programmed can cause this error, depend-
ing on how many points reference the point
function.
1- FAST (.5 sec)
2- PRGRMMD
RESPNS TIME (_ _ _)

Table of Contents

Other manuals for Bosch D7024

Related product manuals