D7024 | Operation and Installation Guide | 7.0 Control Panel Programming
46 Bosch | 7/05 | 31499J
This option allows you to choose the control pattern for
the selected NAC (Ta b l e 21 ).
4. After programming the desired pattern
configuration, the preceding window appears.
Selecting 3 from the PROG NACs Menu prompts
you to enter four zones to activate this output.
5. Enter the desired zone to activate this output and
press [#].
You are prompted to enter up to four zones (A, B,
C, or D).
6. Enter “00” or leave it set at “00” for any unused
zones to prevent unintentional output activation.
When all four zones are programmed, the
preceding window appears.
Remote NACs
Shortcut:
0-PROG > 5-PROG OUTPUTS > 1-NACs
Only use this option with the D7038. The display scrolls
through the NAC options.
1. Press [2] for REMOTE 1 or [3] for REMOTE 2.
One of the following windows appears:
or
2. Press the number key corresponding to the NAC
you want to program.
The display scrolls through the following selections:
The options for remote NACs are the same as for
local NACs, except the Wheelock and Gentex
configuration are not supported on remote NACs.
Table 21: NAC Patterns
NAC Pattern
Steady Output turns on and stays on while the NAC is
active.
Pulsing Output turns on and off each second.
Temporal Output turns on and off to implement the ANSI
standard evacuation pattern (Code 3).
Wheelock Output is configured to support Wheelock
devices with sync capability, including the abil-
ity to silence a horn and strobe combination
horn. The Wheelock configuration is not sup-
ported by remote NACs implemented using a
D7038 Remote NAC Power Supply.
Gentex Output is configured to support Gentex
devices with sync capability, including the abil-
ity to silence a horn and strobe combination
horn. The Gentex configuration is not sup-
ported by remote NACs implemented using a
D7038 Remote NAC Power Supply.
OUTPUT ZONE A (XX)
(00-63):
Table 22: Pre-Assigned Zone Quick Reference
Zone Pre-Assigned Condition
52 General Fire Alarm (non-silencing)
53 General Fire Alarm (silencing)
54 Ground Start
57 Communication Trouble
58 General Supervisory Alarm (non-silencing)
59 Alarm Verification
60 AC Failed
61 General Waterflow Alarm (non-silencing)
62 General Trouble
63 General Fire Alarm, Monitor, Waterflow supervisory
(non-silencing)
“XX” indicates the current setting for each of the four output
zone settings.
REM EXP NAC#1)
1- NAC #1
2- NAC #2
3- NAC #3
4- NAC #4
REM EXP NAC#2)
1- NAC #1
2- NAC #2
3- NAC #3
4- NAC #4
PROG NAC
4- (reserved)
5- CONFIGURATION
6- ZONE ASSIGNS