EasyManua.ls Logo

Bosch D7412G - Figure 3: D9412 G System Wiring Diagram

Bosch D7412G
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
D9412G/D7412G/D7212G Installation & Troubleshooting Quick Reference Guide
Page 24 © 2004 Bosch Security Systems, Inc.43700F
D9412G/D7412G / D7212G
System Wiring Diagrams, Issue A
4.2 D9412G Control Panel, 2 of 3
P105BL
D125B
Sw. Aux Pwr
Zone B
Zone A
Pnl Common
Pnl Common
Loop B-
Loop A-
Loop B+
Loop A+
Earth Ground
10
9
5
4
3
8
2
1
7
6
D129
Aux Power
Zone B
Zone A
Common
Loop B-
Loop A-
Loop B+
Loop A+
Earth Ground
10
9
5
4
3
8
2
1
7
6
11
12
13
Loop A+
Loop A-
Loop B+
Loop B-
P105F
EARTH GROUND
COMMON
BATTERY NEGATIVE ONLY
Maximum Charging
Current 1.4 Amps.
BATTERY POSITIVE ONLY
RELAY A
RELAY B
RELAY C
+ AUX POWER
1
2
3
4
5
6
7
8
9
10
CLASS 2 TRANSFORMER
16.5 VAC 40 VA 60 Hz
Model D1640
Internally Fused - Do Not short
Requires Unswitched Outlet
Do Not Share With Other Equipment
PROGRAMMABLE
ALARM OUTPUTS
Terminal s
Requires Optional
Model D136 Relay
In ALT ALARM
& SW AUX
&
78
GROUND FAULT DETECT
Enabled
Disabled
PHONE
LED
RED
ON WHEN
COMMUNICATING
OFF WHEN IDLE
VOLTAGE RANGES
Open 3.7 - 5.0 VDC
Normal 2.0 - 3.0 VDC
Short 0.0 - 1.3 VDC
GRN
LOOP START
PHONE MONITOR SELECT
Point 8
GND FAULT
Detect
E
N
A
B
L
E
D
I
S
A
B
L
E
1211 13
Point 1 Point 2
1514 16
Point 3 Point 4
1817 19
Point 5 Point 6
2120 22
Point 7 Point 8
GROUND START
Requires Relay
Model D136 i n
Grou nd
Start Socket
GND START
+
-
D130
1
2
5
3
4
Figure 3: D9412G System Wiring Diagram, 2 of 3
1 - (Optional): For 24 V applications, use a UL Listed 24 VDC Power Supply with a D130 Relay Module. Refer to the
D130 Operation and Installation Guide (P/N: 74-06262-000) for correct wiring requirements.
2 - To UL Listed two-wire smoke detectors. Refer to the 9000/9000G Series Technical Service Note: Smoke Detector
Compatibility (P/N: 33284) for a listing of compatible two-wire smoke detectors.
3 - P105F, 1 k
EOLR (P/N: 15-03130-004): Suitable for un-powered initiating and supervisory devices such as pull
stations, heat sensors, and valve tampers.
4 - P105BL, 1 k
EOLR (P/N: 15-03130-004): For typical burglar alarm applications.
5 - D129 provides optional Waterflow Retard feature. Not suitable for two-wire smoke detectors.
(
Note:
Use Zero Retard except for waterflow devices.)

Table of Contents

Other manuals for Bosch D7412G

Related product manuals