D9412GV2/D7412GV2 | Operation and Installation Guide | Appendix A: System Wiring Diagrams, Issue A
.
Bosch Security Systems, Inc. | 7/09 | F01U003641-04 69
Appendix A: System Wiring Diagrams, Issue A
A.1 D9412GV2 Control Panel
Figure 38: D9412GV2, Power Supply Side
TELC O
RI NGTI P
PH ONE L INE
SEIZED
+
AUX PWR
ALARM TRIG
COM
SUPV IN
ALA R M C K T
-
- +
D113
BA T 2 +
BAT 1+
BA T 2 -
BA T 1 - SUPV
CH G R +
CHGR-
VA UX +
- +
-
+
- +
EARTH GROUND
CO MMON
BATTERY NEGATIVE ONLY
Maximum Charg ing
C u rr en t 1. 4 A mp s.
BATTERY POSITIVE ONLY
RELAY A
RELAY B
RELAY C
+ AUX POW E R
1
2
3
4
5
6
7
8
9
10
CLASS 2 TRANSF ORMER
16.5 VAC 40 VA 60 Hz
Mod el D164 0
Interna lly Fu sed - Do Not short
Requ ires Unswitched Outlet
Do No t S har e Wi th O ther Equipment
GROUND FAULT DETECT
Enabled
Disabled
1211 13
Po int 1 Point 2
1514 16
Po int 3 Point 4
PH ONE
LE D
RED
ON when
communicating
OFF whe n idle
PH ONE LINE SEIZED
TI P R ING
TELC O CO RD
MODE L D161
GRN
Point 8
S3 Option
Clo sed = 1K
Ω
EOL
Normal O perat i on
Open =AB-12 UL
Bell Bo x 220 K
Ω
D5 2 00 / D5 3 6 0
PR O G CO N N
PROGRAMM ABLE
ALARM OUTPUTS
Terminals
SWITCHED AUX
and67
Terminal
8
11
13
14
16
12
10
2
6
7
9
66
2
2 2
3
2
5
4
6
6
6
8
15
D9412GV2
1 - If required by local AHJ, connect D113 Battery
Lead Supervision Module.
2 Batteries
3 - D122 Dual Battery Harness, as required
4- D1640 Transformer and D8004 Transformer
Enclosure required for NFPA Applications
5 - D8132 Dual Battery Charger with two batteries
(Batteries are not supervised.)
6 - Power limited, supervised
7 - Power limited
8 - D192G Bell Supervision Module
9 - To Relay A or Relay B
10 - Listed Audible Signaling Devices rated at
12.0 VDC nominal (Do not use vibrating type
horns.)
11 - C900V2 or C900TTL-E (optional)
12 - RJ31X, secondary phone line
13 - 560
Ω
, 2 W EOL Resistor
14 - RJ31X, primary phone line
15 - D928
16 - To earth ground
All external connections except Terminal 5 (battery positive) are power limited.

Table of Contents