5.0 Configuration
5.1 Program Jumper for the S/U Control
Terminal
Use the S/U control terminal as an alarm memory
control input by setting the jumper in the upper position
as shown in Item 1 of Figure 6.
Use the S/U control terminal as an electronic alarm
output (open collector) by setting the jumper in the
lower position as shown in Item 2 of Figure 6.
5.2 User DIP Switches
5.3 Adjusting Sensitivity
Table 1: Sensitivity Settings
DIP Switch 2 OFF
Standard Sensitivity (Default):
Recommended for maximum false
alarm prevention.
Tolerates environmental extremes.
Not recommended for curtain
patterns.
DIP Switch 2 ON
Intermediate Sensitivity:
Recommended for any location
where an intruder is expected to
cover only a small portion of the
protected area, or when you want
improved catch performance.
Does not tolerate normal
environments.
5.4 LED Setup Without S/U and WT
Remote Control Panel Inputs
Table 2: LED Setup Without Control Panel Inputs
DIP Switch Settings
LED
Operation
User DIP Switch 1
Walk Test
User DIP Switch 3
Set/Unset
Disable LED Any ON
Enable LED OFF (default)
OFF (default)
5.0 Configuration
Figure 7: User DIP Switches
3
1
2
12 3
OPEN
1 - Walk Test polarity (Refer to Section 5.4 LED
Setup Without S/U and WT Remote Control
Panel Inputs.)
2 - Sensitivity (Refer to Section 5.5 Setup for
Remote Control Alarm Memory and LED
Operation Using S/U and WT Inputs.)
3 - Set/Unset polarity (Refer to Section 5.4.)
1 - Alarm memory control input
2 - Electronic alarm output
Figure 6: Program Jumper Settings
2
1
S/U
AL
S/U
AL
DS304| Installation Instructions |